Colt International from Cuijk develops tunnel systems to ensure fire safety at Station Delft

Vialis B.V. and Van Hattum en Blankenvoort B.V., both part of Koninklijke VolkerWessels, are carrying out the fit-out and installing the tunnel systems at Tunnel Delft, the second phase of the NS station in Delft. Tunnel Delft as a whole, phases 1 and 2, will open to rail traffic between The Hague and Rotterdam in 2025. Passenger safety at Delft station is paramount, particularly in the event of a fire. Colt International from Cuijk is closely involved in delivering the smoke control system at the station, the ventilation system in the tunnels and the pressurisation systems in the emergency stairwells, to ensure fire safety in the tunnels and station.
Koninklijke VolkerWessels starts fit-out of second phase of Station Delft
Improvements to the The Hague–Rotterdam rail corridor are part of the Programme for High-Frequency Rail Transport (PHS), under which ProRail is progressively upgrading the busiest rail routes in the Netherlands to accommodate more trains. Doubling the track between Rijswijk and Delft Zuid, and upgrading infrastructure and signalling between Delft Zuid and Rotterdam, will make it possible to run eight intercity trains and six local trains per hour in each direction on this route in 2025. This will enable passengers to catch a train between Rotterdam and The Hague every five minutes. The first tunnels, with tracks 1 and 2, entered service in 2015. Fit-out and installation of the tunnel systems in the third and fourth tunnels began in mid-2019. VolkerWessels is also continuing work on the underground platform, which lies between the four tunnels. This second phase of the project is due for completion at the end of 2024, ready for high-frequency rail services. An estimated 40,000 passengers will then board or alight at Delft on an average working day.
Stan Veldpaus is a fire safety project adviser at Colt International in Cuijk, a manufacturer of smoke control systems, climate control systems and solar shading. Colt specialises in developing smoke control systems such as smoke and heat exhaust ventilation (SHEV) systems, pressurisation systems and jet fan ventilation systems for both above-ground and underground buildings and tunnels. For Tunnel Delft, Colt developed the smoke control systems for the station, tunnels and emergency stairwells, and will maintain them in full after handover. “Installing ventilation in the four tunnels and the station is quite complex because they are all interconnected and need to operate together. The ventilation systems must work in such a way that, in the event of a fire anywhere, smoke is kept to a minimum in both the station, including the platforms, and the tunnels,” says Veldpaus. “This requires jet fans in the tunnels and mechanical smoke extract fans in the station. Together, they need to remove smoke and heat as effectively as possible,” Veldpaus explains.
For both phases, the installation designs for the systems described above have been optimised using CFD models (computational fluid dynamics). “The simulations were produced in-house at Colt by specialists in fluid dynamics,” says Veldpaus. “They predict the effects of airflows in a tunnel and the station in the event of a fire. The computer therefore shows how airflow affects visibility and heat development.” In the event of a fire, smoke and heat must be removed quickly. Smoke and heat are extracted by the SHEV system serving the platforms and concourse, together with the jet fans in the tunnels. This maintains sufficient visibility for passengers and staff to escape quickly and safely. The systems also enable the fire service to locate and extinguish the fire quickly. They therefore control the greatest danger immediately after a fire breaks out, giving passengers and staff significantly more time to escape,” says Veldpaus.
Colt is also responsible for the pressurisation systems in the emergency stairwells adjoining the tunnels. By creating a strong airflow from the stairwell towards the tunnel, smoke is prevented from entering the stairwell. In addition, the pressure difference prevents smoke from entering when the door is closed. The different designs of the stairwells mean that several types of pressurisation system are used on this project. Each system has been designed, installed and tested for its respective stairwell.
Koninklijke VolkerWessels companies Vialis and Van Hattum en Blankevoort are responsible for installing the tunnel systems and completing the fit-out of the second phase of Station Delft. As in the first phase, Colt’s smoke and heat control systems will also be installed in phase two. Marcel van Stek is a project buyer at Vialis and is involved in the tunnel systems. In addition to installing the ventilation, Vialis, as systems integrator, must also ensure that the fire safety systems and installations are interconnected. “Vialis will install 19 jet fans in each of tunnels 3 and 4. Tunnels 1 and 2 have 38 identical fans. Ultimately, all 76 jet fans across the four tunnels will be interconnected, and linked to the SHEV systems on the platforms and in the concourse,” says van Stek. These installations draw in air and push it in one direction with a certain force. The number of jet fans depends on the tunnel’s geometry. “The force is sufficient to drive air in one direction along the tunnel when smoke and heat develop, moving it outside in the direction of travel. This prevents smoke and heat from reaching the platforms and central areas,” he explains. The four emergency stairwells leading from the tunnels to ground level are fitted with standalone pressurisation systems. “Tunnels 3 and 4 will also have four additional emergency stairwells, where Vialis will install the same standalone pressurisation systems from Colt. These systems keep smoke and heat out of the stairwells and blow it back into the tunnel. They ensure passengers can get out of the tunnels as quickly as possible in an emergency,” says van Stek.
Fire ventilation is one of the most important aspects of Tunnel Delft. “It is a major advantage that Colt also designed and supplied the tunnel systems for the first phase,” says van Stek. Using technical information and data from computer simulations, Colt has developed and optimised the smoke control and smoke and heat exhaust systems with great precision. “The close involvement and solution-focused approach demonstrated are testament to Colt’s strength as a reliable supply chain partner on complex projects such as Tunnel Delft,” says van Stek.